Earth Fault Loop Impedance Calculator
Calculate Earth Fault Loop Impedance (Zs) for electrical circuits. Checks compliance with breaker types (B, C, D) and BS 7671 standards.
About
In electrical installations, the Earth Fault Loop Impedance (Zs) is a critical safety parameter. It determines whether a circuit breaker will trip fast enough (usually within 0.4s for TN systems) during a fault to ground. If the impedance is too high, the fault current will be too low to trigger the magnetic trip of the MCB, creating a fire hazard or shock risk.
This tool calculates the total impedance by combining the external impedance (Ze) with the resistance of the Phase and Earth conductors (R1 + R2). It accounts for temperature rise during faults (using a factor of 1.2) and conductor material (Copper or Aluminum). The result is automatically validated against standard "Max Zs" tables for Type B, C, and D breakers according to IEC/BS standards.
Formulas
The formula for Total Loop Impedance is:
Zs = Ze + [ L × (r1 + r2)1000 × Ct ]
Where:
- Ze: External earth loop impedance (from supply).
- L: Length of circuit (meters).
- r1, r2: Resistance per meter of Phase/Earth (mΩ/m).
- Ct: Temperature correction factor (typically 1.2 for operating temp).
Reference Data
| Breaker Type | Current (In) | Max Zs (0.4s) @ 230V | Magnetic Trip |
|---|---|---|---|
| Type B | 6A | 7.28 Ω | 3 - 5 x In |
| Type B | 10A | 4.37 Ω | 3 - 5 x In |
| Type B | 32A | 1.37 Ω | 3 - 5 x In |
| Type C | 6A | 3.64 Ω | 5 - 10 x In |
| Type C | 10A | 2.19 Ω | 5 - 10 x In |
| Type C | 32A | 0.68 Ω | 5 - 10 x In |
| Type D | 6A | 1.82 Ω | 10 - 20 x In |
| Type D | 32A | 0.34 Ω | 10 - 20 x In |