User Rating 0.0
Total Usage 0 times
Ω (Ohms) - Measured at source
Is this tool helpful?

Your feedback helps us improve.

About

In electrical installations, the Earth Fault Loop Impedance (Zs) is a critical safety parameter. It determines whether a circuit breaker will trip fast enough (usually within 0.4s for TN systems) during a fault to ground. If the impedance is too high, the fault current will be too low to trigger the magnetic trip of the MCB, creating a fire hazard or shock risk.

This tool calculates the total impedance by combining the external impedance (Ze) with the resistance of the Phase and Earth conductors (R1 + R2). It accounts for temperature rise during faults (using a factor of 1.2) and conductor material (Copper or Aluminum). The result is automatically validated against standard "Max Zs" tables for Type B, C, and D breakers according to IEC/BS standards.

Zs calculator electrical engineering BS 7671 loop impedance phase-zero loop

Formulas

The formula for Total Loop Impedance is:

Zs = Ze + [ L × (r1 + r2)1000 × Ct ]

Where:

  • Ze: External earth loop impedance (from supply).
  • L: Length of circuit (meters).
  • r1, r2: Resistance per meter of Phase/Earth (mΩ/m).
  • Ct: Temperature correction factor (typically 1.2 for operating temp).

Reference Data

Breaker TypeCurrent (In)Max Zs (0.4s) @ 230VMagnetic Trip
Type B6A7.28 Ω3 - 5 x In
Type B10A4.37 Ω3 - 5 x In
Type B32A1.37 Ω3 - 5 x In
Type C6A3.64 Ω5 - 10 x In
Type C10A2.19 Ω5 - 10 x In
Type C32A0.68 Ω5 - 10 x In
Type D6A1.82 Ω10 - 20 x In
Type D32A0.34 Ω10 - 20 x In

Frequently Asked Questions

If Zs exceeds the maximum limit, the breaker may not trip within the required safety time (0.4s or 5s). You must either increase the cable cross-section (to lower resistance), reduce the circuit length, change the breaker curve (e.g., C to B), or install an RCD (Residual Current Device).
Ze (External Impedance) depends on your transformer and grid connection. It is measured at the distribution board. Typical values are 0.35 Ω for TN-C-S systems and 0.8 Ω for TN-S systems, but you should measure it with a tester.
Phase-Zero is a term used in some regions (like Eastern Europe/Russia) equivalent to the Earth Fault Loop. It refers to the complete circuit path from the transformer phase, through the fault, and back via the neutral/earth (zero) conductor.
Standard resistance is given at 20°C. However, when a circuit is loaded or faulting, the cable heats up. As temperature rises, resistance increases. The factor of 1.2 adjusts the calculation to reflect "operating temperature" (approx 70°C) for a worst-case safety scenario.