User Rating 0.0
Total Usage 0 times
Is this tool helpful?

Your feedback helps us improve.

About

Selecting the correct circuit breaker is a matter of fire safety. A breaker that is too small will trip unnecessarily (nuisance tripping), while a breaker that is too large may fail to interrupt a fault before the wire insulation melts. This tool calculates the required breaker size based on the connected load (Watts), Voltage, and Power Factor.

Crucially, this calculator adheres to the 80% Rule (NEC Standard). For continuous loads (running 3+ hours), the circuit breaker should be sized so that the load does not exceed 80% of the breaker's rating. Inversely, the minimum breaker size must be 125% of the continuous load current. This tool outputs both the raw calculated amps and the next standard commercial breaker size available.

electrical engineering NEC code amperage load calculator circuit protection

Formulas

First, calculate Load Current (Iload). For Single Phase AC:

Iload = PV × PF

For Three Phase AC:

Iload = P3 × V × PF

Then, determine Minimum Breaker Rating (Icb):

Icb Iload × 1.25

Reference Data

Breaker Size (Amps)Typical Wire Gauge (Copper)Max Continuous Load (80%)
15 A14 AWG12 A
20 A12 AWG16 A
30 A10 AWG24 A
40 A8 AWG32 A
50 A6 AWG40 A
60 A4 AWG48 A
100 A3 AWG80 A
200 A2/0 AWG160 A

Frequently Asked Questions

The National Electrical Code (NEC) states that a circuit breaker should not handle a continuous load (3 hours or more) higher than 80% of its rating. Effectively, this means you multiply your load by 1.25 to find the breaker size.
You must round up. For example, if the calculation calls for a 17 Amp breaker, you cannot buy one. You must use the next standard size up, which is 20 Amps, provided the wire gauge is also upgraded to match.
A lower Power Factor (e.g., 0.8) draws more current (Amps) to do the same amount of work (Watts) compared to a PF of 1.0. This "wasted" current flows through the breaker, so the breaker must be sized larger to handle it.