User Rating 0.0
Total Usage 0 times
Category Electronics
A
Amperage draw of the circuit
V
Nominal voltage (120, 240, 208, 480)
ft
Distance from panel to load
Copper is standard residential
Check wire jacket markings
Residential is typically single
Quick Presets:
Is this tool helpful?

Your feedback helps us improve.

About

Undersized conductors cause resistive heating proportional to I2 × R. This is not an inconvenience. It is the ignition mechanism behind thousands of residential electrical fires annually. NEC Table 310.16 specifies maximum allowable ampacities for insulated conductors rated 0 - 2000 V, and compliance is not optional. This calculator performs a direct ceiling-match lookup against that table for both copper and aluminum conductors across 60°C, 75°C, and 90°C insulation temperature ratings. It then validates the result against NEC’s recommended maximum 3% voltage drop threshold for branch circuits given your one-way run distance and system voltage.

The tool assumes no more than three current-carrying conductors in a raceway at an ambient temperature of 30°C. Derate factors for conduit fill, ambient temperature above 30°C, or continuous loads (125% rule) are the user’s responsibility. Pro tip: for continuous loads exceeding 3 hours, multiply your amperage by 1.25 before entering it here.

wire size calculator amp to awg wire gauge calculator NEC wire sizing electrical wire calculator ampacity table voltage drop calculator

Formulas

Wire sizing follows a two-step process: ampacity matching and voltage drop verification.

Step 1 - Ampacity Match: Select the smallest AWG gauge from NEC Table 310.16 where:

Irated Iload

Step 2 - Voltage Drop Check:

Vdrop = 2 × L × I × ρA

Vdrop% = VdropVsource × 100

If Vdrop% > 3%, upsize the conductor until the threshold is met.

Where L = one-way cable run length in ft, I = load current in A, ρ = conductor resistivity in Ω⋅ft, A = cross-sectional area in cmil, and Vsource = system voltage. The factor of 2 accounts for the complete circuit (hot + neutral). For 3-phase circuits, replace 2 with 1.732 (3).

Reference Data

AWGArea (kcmil)Cu 60°C (A)Cu 75°C (A)Cu 90°C (A)Al 60°C (A)Al 75°C (A)Al 90°C (A)Ω/1000ft CuTypical Use
181.6271014 - - - 6.385Thermostats, doorbells
162.58101318 - - - 4.016Extension cords (light)
144.11152025 - - - 2.52515A branch circuits, lighting
126.532025301520251.58820A branch circuits, outlets
1010.383035402530350.999Dryers, water heaters, 30A circuits
816.514050553040450.628Ranges, large appliances
626.245565754050600.395A/C units, sub-panels
441.747085955565750.249Feeders, large A/C
352.62851001156575850.197Service entrance
266.369511513075901000.156Service entrance, feeders
183.69110130145851001150.124Service entrance, sub-panels
1/0105.61251501701001201350.098200A residential service
2/0133.11451751951151351500.078200A service, feeders
3/0167.81652002251301551750.062Large feeders, commercial
4/0211.61952302601501802050.049200A+ service entrance
250 kcmil2502152552901702052300.042Commercial feeders
300 kcmil3002402853201902302550.035Large commercial service
350 kcmil3502603103502102502800.029Industrial feeders
400 kcmil4002803353802252703050.026Industrial service
500 kcmil5003203804302603103500.021Heavy industrial

Frequently Asked Questions

The insulation temperature rating determines how much heat the conductor can dissipate before insulation degradation occurs. A wire rated at 90°C (e.g., THHN) can carry more current than the same gauge rated at 60°C (e.g., TW) because its insulation tolerates higher operating temperatures. However, NEC 110.14(C) restricts termination ratings: most residential terminals are rated 75°C, so you must use the 75°C column even with 90°C wire unless the equipment is specifically listed for higher temperatures.
NEC 210.20(A) requires that conductors supplying continuous loads (loads expected to run for 3 hours or more) be sized at 125% of the continuous load current. For example, a 40A continuous load requires wire rated for at least 50A. Enter 50 into this calculator if your 40A load is continuous.
Voltage drop increases linearly with distance per Vdrop = 2 × L × I × R. NEC recommends no more than 3% drop for branch circuits and 5% total for feeder plus branch. A 20A circuit on 12 AWG copper is fine at 50ft, but at 150ft you may need to upsize to 10 AWG or even 8 AWG to stay within 3%.
Yes, but aluminum has approximately 61% the conductivity of copper, so you typically need to go up 2 AWG sizes. Aluminum also requires anti-oxidant compound at terminations and connectors rated for AL/CU. Aluminum is common and cost-effective for service entrance cables (e.g., SER) and large feeders above 4 AWG. NEC prohibits aluminum for 18, 16, and 14 AWG branch circuits.
This calculator uses NEC Table 310.16 baseline values assuming no more than 3 current-carrying conductors in a raceway at 30°C ambient. You must manually apply NEC Table 310.15(C)(1) for ambient temperatures above 30°C and Table 310.15(C)(1) for conduit fill with more than 3 conductors. For example, 4 - 6 conductors in a conduit require an 80% derating factor.
Yes. For single-phase circuits, the formula uses a multiplier of 2 (hot + neutral). For 3-phase circuits, the multiplier is 3 (1.732). This calculator supports both configurations. The 3% recommendation still applies per NEC 210.19(A) Informational Note No. 4, though the actual drop will be lower in a balanced 3-phase system.