Amp to Wire Size Calculator
Calculate the correct wire gauge (AWG) for any amperage load. Uses NEC Table 310.16 for copper and aluminum conductors with voltage drop analysis.
About
Undersized conductors cause resistive heating proportional to I2 × R. This is not an inconvenience. It is the ignition mechanism behind thousands of residential electrical fires annually. NEC Table 310.16 specifies maximum allowable ampacities for insulated conductors rated 0 - 2000 V, and compliance is not optional. This calculator performs a direct ceiling-match lookup against that table for both copper and aluminum conductors across 60°C, 75°C, and 90°C insulation temperature ratings. It then validates the result against NEC’s recommended maximum 3% voltage drop threshold for branch circuits given your one-way run distance and system voltage.
The tool assumes no more than three current-carrying conductors in a raceway at an ambient temperature of 30°C. Derate factors for conduit fill, ambient temperature above 30°C, or continuous loads (125% rule) are the user’s responsibility. Pro tip: for continuous loads exceeding 3 hours, multiply your amperage by 1.25 before entering it here.
Formulas
Wire sizing follows a two-step process: ampacity matching and voltage drop verification.
Step 1 - Ampacity Match: Select the smallest AWG gauge from NEC Table 310.16 where:
Irated ≥ Iload
Step 2 - Voltage Drop Check:
Vdrop = 2 × L × I × ρA
Vdrop% = VdropVsource × 100
If Vdrop% > 3%, upsize the conductor until the threshold is met.
Where L = one-way cable run length in ft, I = load current in A, ρ = conductor resistivity in Ω⋅ft, A = cross-sectional area in cmil, and Vsource = system voltage. The factor of 2 accounts for the complete circuit (hot + neutral). For 3-phase circuits, replace 2 with 1.732 (√3).
Reference Data
| AWG | Area (kcmil) | Cu 60°C (A) | Cu 75°C (A) | Cu 90°C (A) | Al 60°C (A) | Al 75°C (A) | Al 90°C (A) | Ω/1000ft Cu | Typical Use |
|---|---|---|---|---|---|---|---|---|---|
| 18 | 1.62 | 7 | 10 | 14 | - | - | - | 6.385 | Thermostats, doorbells |
| 16 | 2.58 | 10 | 13 | 18 | - | - | - | 4.016 | Extension cords (light) |
| 14 | 4.11 | 15 | 20 | 25 | - | - | - | 2.525 | 15A branch circuits, lighting |
| 12 | 6.53 | 20 | 25 | 30 | 15 | 20 | 25 | 1.588 | 20A branch circuits, outlets |
| 10 | 10.38 | 30 | 35 | 40 | 25 | 30 | 35 | 0.999 | Dryers, water heaters, 30A circuits |
| 8 | 16.51 | 40 | 50 | 55 | 30 | 40 | 45 | 0.628 | Ranges, large appliances |
| 6 | 26.24 | 55 | 65 | 75 | 40 | 50 | 60 | 0.395 | A/C units, sub-panels |
| 4 | 41.74 | 70 | 85 | 95 | 55 | 65 | 75 | 0.249 | Feeders, large A/C |
| 3 | 52.62 | 85 | 100 | 115 | 65 | 75 | 85 | 0.197 | Service entrance |
| 2 | 66.36 | 95 | 115 | 130 | 75 | 90 | 100 | 0.156 | Service entrance, feeders |
| 1 | 83.69 | 110 | 130 | 145 | 85 | 100 | 115 | 0.124 | Service entrance, sub-panels |
| 1/0 | 105.6 | 125 | 150 | 170 | 100 | 120 | 135 | 0.098 | 200A residential service |
| 2/0 | 133.1 | 145 | 175 | 195 | 115 | 135 | 150 | 0.078 | 200A service, feeders |
| 3/0 | 167.8 | 165 | 200 | 225 | 130 | 155 | 175 | 0.062 | Large feeders, commercial |
| 4/0 | 211.6 | 195 | 230 | 260 | 150 | 180 | 205 | 0.049 | 200A+ service entrance |
| 250 kcmil | 250 | 215 | 255 | 290 | 170 | 205 | 230 | 0.042 | Commercial feeders |
| 300 kcmil | 300 | 240 | 285 | 320 | 190 | 230 | 255 | 0.035 | Large commercial service |
| 350 kcmil | 350 | 260 | 310 | 350 | 210 | 250 | 280 | 0.029 | Industrial feeders |
| 400 kcmil | 400 | 280 | 335 | 380 | 225 | 270 | 305 | 0.026 | Industrial service |
| 500 kcmil | 500 | 320 | 380 | 430 | 260 | 310 | 350 | 0.021 | Heavy industrial |